February 2012
Used 70000 PPH, Nebraska, 300 PSI, Low NOx, Gas, #2 oil, 2.5 ppm Ultra-Low NOx  option, 1995                                                                          UED

Nationwide Boiler Inc
42400 Christy St
Fremont CA 94538-4401
Tel: 800-227-1966 Fax: 510-490-0571
lday@nationwideboiler.com  www.nationwideboiler.com

70000 PPH, Nebraska, 300 PSI, Low NOx, Gas, #2 oil, 2.5 ppm Ultra-Low NOx option, 1995 [438]

70000 PPH, Nebraska, 300 PSI, Low NOx, Gas, #2 oil, 2.5 ppm Ultra-Low NOx option, 1995

Nationwide Boiler’s low NOx 70,000 pph, 300 psig design, saturated steam, trailer-mounted packa
e watertube boiler is set to burn natural gas or #2 oil. It is fully piped and wired and includes th
following components:

Low NOx Burner
Burner Management System
Single-point Positioning Combustion Controls
Forced Draft Fan, Motor & Starter
Complete Fuel Train & Pilot Ignition System
#2 Fuel Oil Pump
Water Column & Site Glass
Steam Pressure Gauge
Low-water Cutoffs
Safety Valves
Feedwater Stop & Check Valves
Blowdown Valves
Continuous Blowdown Metering Valve
Chemical Feed Valve
Single Element Feedwater Regulator with Pre-piped
3-Valve Bypass
Steam Non-return Valve
Stack (loose)
NEMA 4 Electrical Enclosures
EconoStak Economizer (optional)
Low NOx CataStak™ SCR System (optional)
Weatherproofed (except for freezing)
Meets FM, NFPA 85 & IRI Insurance Standards
Operating Manuals

Fuel Consumption:
Natural Gas: 92,700 SCFH @ 10 psi regulated
#2 Oil: 617 GPH

Connection Sizes:
Main Steam: 8"-300# FLG
Natural Gas: 4"-150# FF FLG
#2 Oil Supply / Return: 1½" NPT / ¾" NPT
Feedwater: 2½"-300# FLG
Bottom Blowdown: 1½"-300# FLG
Continuous Blowdown: 1" NPT
Chemical Feed: 1" NPT
Atomizing Air / Steam: 1" NPT / 1¼" NPT
Instrument Air: ¼" NPT
Water Column Drain: ¾" NPT

Electrical Power Service Requirements:
480 VAC, 3 ph, 60 hz, 200 amp

Dimensions & Weights:
Length / Width / Height: 52' 0" / 10' 7" / 14' 0"
Shipping Weight: 85,000 lbs
Operating Height: 102,600 lbs

Emissions Data (natural gas):
NOx (corr. to 3%2): 30 ppm
CO (corr. to 3%2): 50 ppm